# Simulation overlay for testing without physical hardware # Usage: esphome run rack-fan-controller.yaml # Then use HA developer tools to set simulated sensor values # # This file documents how to test the controller logic # without real DS18B20 sensors or fans connected. # # Method 1: ESPHome dashboard # - Flash the normal config to any ESP32-C6 # - The sensors will show "unknown" but the control loop # handles missing sensors gracefully (defaults to 50% duty) # - Use HA number entities to adjust target temp and duty limits # # Method 2: Home Assistant template sensors # Add these to your HA configuration.yaml to simulate temps: # # input_number: # sim_rack_temp_intake: # name: "Sim Rack Temp Intake" # min: 15 # max: 70 # step: 0.5 # initial: 25 # unit_of_measurement: "C" # sim_rack_temp_central: # name: "Sim Rack Temp Central" # min: 15 # max: 70 # step: 0.5 # initial: 30 # unit_of_measurement: "C" # sim_rack_temp_outtake: # name: "Sim Rack Temp Outtake" # min: 15 # max: 70 # step: 0.5 # initial: 27 # unit_of_measurement: "C" # # Method 3: Test the display layout # Flash to the real Waveshare ESP32-C6 board (even without # sensors/fans connected). The display will render with # "--.-C" placeholders and you can verify the layout. # # Expected behavior matrix: # temp < 28C -> duty = min_duty (default 20%) # temp = 35C -> duty ~= 50% (midpoint of default ramp) # temp = 42C -> duty ~= 80% # temp > 43C -> duty = max_duty (default 100%) # temp > 50C -> overheat alert triggers # no sensors -> duty = 50% (safety fallback)